同塔四回输电线路的电气间隙瓶颈
          
Tower with Four Transmission Lines’ Electrical Gap Bottleneck

黄 平  
摘    要
以无锡地区220 kV同塔四回输电线路工程为例,通过分析线路在“四变二”时遇到的电气间隙问题,提出了构建三维坐标模型,将线路分割为节点坐标化校验的设计思路和方案。阐述了三维坐标模型的构建方式,将多相电线复杂交错的抽象空间转化为寻找两条轨迹之间最小距离的数学问题,较为直观准确地保证了输电线路电气安全。
标    签 同塔四回路   电气间隙   三维坐标模型   Tower with four transmission lines   Electrical gap   Three dimensional coordinate model  
 
Abstract
Take Wuxi area’s 220kV tower with four transmission lines as an example, through analyzes this kind of line when “four change two” meets the electrical gap question, proposed the construction three dimensional coordinate model initially, line division for node coordinate verification design mentality and plan. This article elaborated the three dimensional coordinate model’s construction way, transforms the heterogeneity electric wire complex staggered abstract space to seek between two paths the minimum range mathematics question, the more directviewing accurate guarantee transmission line electricity security.

中图分类号 TM751

 
  购买该论文  中国光学期刊网论文下载说明


所属栏目 电力技术

基金项目

收稿日期 2014/6/29

修改稿日期

网络出版日期

作者单位点击查看

备注黄 平(1981),男,工程师,从事电网线路电气设计工作。

引用该论文: Huang Ping. Tower with Four Transmission Lines’ Electrical Gap Bottleneck[J]. Power & Energy, 2014, 35(6): 741~744
黄 平. 同塔四回输电线路的电气间隙瓶颈[J]. 电力与能源, 2014, 35(6): 741~744